Powerflex 7000 drive selection explanation – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control User Manual

Page 163

Advertising
background image

Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014

163

Catalog Number Explanation

Appendix B

PowerFlex 7000 Drive
Selection Explanation

The PowerFlex 7000 medium voltage AC drive selection tables are based on two
types of drive service duty ratings:

1. Normal Duty (110% overload for one minute, once every ten minutes)

– used for Variable Torque (VT) applications only.

Drives with this rating are designed for 100% continuous operation, with
110% overload for one minute, once every ten minutes.

2. Heavy Duty (150% overload for one minute, once every ten minutes)

used for Constant Torque (CT) applications only.

Drives with this rating are designed for 100% continuous operation with
150% overload for one minute, once every ten minutes.

Service Duty Rating, Continuous Current Rating and
Altitude Rating Code

There are different codes that define service duty and altitude in the drive catalog
number (see

Catalog Number Explanation on page 161

).

EXAMPLE

Catalog number 7000A – A105DED-RPDTD, has a continuous current rating of
105 A, with a “normal duty” service rating up to 1000 m altitude.

Catalog number 7000A – B105DED-RPDTD has a continuous rating of 105 A
with a “normal duty” service rating up to 5000 m altitude.

The ambient temperature rating is reduced at higher altitudes. If 40 °C ambient
is required at 1001...5000 m altitude, a rating code of Z is required.

Advertising