Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control User Manual

Page 40

Advertising
background image

40

Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014

Chapter 2

Drive Installation

Table 1 - Wire Group Numbers

Belden 8760 - 18 AWG, twisted pair, shielded
Belden 8770 - 18 AWG, 3 conductor, shielded
Belden 9460 - 18 AWG, twisted pair, shielded
Belden 9463 - 24 AWG, twisted pair, shielded

Note 1: Steel conduit or cable tray may be used for all PowerFlex 7000 Drive power or control wiring, and steel conduit is required for all

PowerFlex 7000 Drive signal wiring. All input and output power wiring, control wiring or conduit should be brought through the
drive conduit entry holes of the enclosure. Use appropriate connectors to maintain the environmental rating of the enclosure. The
steel conduit is REQUIRED for all control and signal circuits, when the drive is installed in European Union countries. The connection
of the conduit to the enclosure shall be on full 360 degree and the ground bond at the junction shall be less than 0.1 ohms. In EU
countries this is a usual practice to install the control and signal wiring.

Note 2: Spacing between wire groups is the recommended minimum for parallel runs of 61 m (200 ft) or less.
Note 3: The customer is responsible for the grounding of shields. On drives shipped after November 28/02, the shields are removed from

the drive boards. On drives shipped prior to November 28/02, all shields are connected at the drive end and these connections must
be removed before grounding the shield at the customer end of the cable. Shields for cables from one enclosure to another must be
grounded only at the source end cabinet. If splicing of shielded cables is required, the shield must remain continuous and insulated
from ground.

Note 4: AC and DC circuits must be run in separate conduits or trays.

Note 5: Voltage drop in motor leads may adversely affect motor starting and running performance. Installation and application

requirements may dictate that larger wire sizes than indicated in IEC / NEC guidelines are used.

For Tray:

Recommended spacing between different wire groups in the same tray.

For Conduit: Recommended spacing for wire groups in separate conduit – mm (inches)

Wire

Category

Wire

Group

Application

Signal Example

Recommended

Cable

Wire

Group

Power

1

Power

2

Control

3

Control

4

Signal

5

Signal

6

Power

1

AC Power

(> 600V AC)

2.3 kV, 3Ø

AC Lines

Per IEC / NEC

Local Codes and

Application

Requirements

In Tray

228.6

(9.00)

228.6

(9.00)

228.6

(9.00)

228.6

(9.00)

Between

Conduit

76.2 (3.00)

Between Conduit

2

AC Power

(TO 600V AC)

480V, 3Ø

Per IEC / NEC

Local Codes and

Application

Requirements

In Tray

228.6

(9.00)

228.6

(9.00)

152.4

(6.00)

152.4

(6.00)

Between

Conduit

76.2 (3.00)

Between Conduit

Control

3

115V AC

or 115V DC

Logic

Relay Logic

PLC I/O

Per IEC / NEC

Local Codes and

Application

Requirements

In Tray

228.6

(9.00)

152.4

(6.00)

228.6

(9.00)

152.4

(6.00)

115V AC

Power

Power Supplies

Instruments

Between

Conduit

76.2 (3.00)

Between Conduit

4

24V AC

or 24V DC

Logic

PLC I/O

Per IEC / NEC

Local Codes and

Application

Requirements

In Tray

228.6

(9.00)

152.4

(6.00)

152.4

(6.00)

228.6

(9.00)

Between

Conduit

76.2 (3.00) Between Conduit

Signal

5

Analog Signals

DC Supplies

5-24V DC

Supplies

Belden 8760
Belden 8770
Belden 9460

Digital

(Low Speed)

Power Supplies

TTL Logic Level

All signal wiring must be run in separate steel conduit.
A wire tray is not suitable.
The minimum spacing between conduits containing different
wire groups is 76.2 mm (3 inches).

6

Digital

(High Speed)

Pulse Train

Input Tachometer

PLC

Communications

Belden 8760
Belden 9460
Belden 9463

Advertising