Snubber Resistance

Access to the snubber resistor is not required to test its resistance. Located
within the PowerCage under the heatsink is a snubber circuit test point. For each
device, there is one test point. To verify the resistance, measure the resistance
between the test point and the heat sink above.

Figure 58 - Testing the Snubber Resistor

Figure 59 - Snubber Resistor Test (with SPS Board)

Snubber test point

Measure resistance
between heat sink
and test point

Heatsink

Heatsink

SGCT

Snubber
Resistor

Snubber
Capacitor

Sharing Resistor

Test Point

Resistance value between
heat sink and test point is
Snubber Resistance

Heatsink

Heatsink

Snubber
Resistor

Snubber
Capacitor

Sharing Resistor

J1

SPS Board

1

2

SGCT

Test Point

Resistance Value between two
heat sinks is sharing resistance
in parallel with Anode-Cathode
Resistance