Snubber Resistance
Access to the snubber resistor is not required to test its resistance. Located
within the PowerCage under the heatsink is a snubber circuit test point. For each
device, there is one test point. To verify the resistance, measure the resistance
between the test point and the heat sink above.
Figure 58 - Testing the Snubber Resistor
Figure 59 - Snubber Resistor Test (with SPS Board)
Snubber test point
Measure resistance
between heat sink
and test point
Heatsink
Heatsink
SGCT
Snubber
Resistor
Snubber
Capacitor
Sharing Resistor
Test Point
Resistance value between
heat sink and test point is
Snubber Resistance
Heatsink
Heatsink
Snubber
Resistor
Snubber
Capacitor
Sharing Resistor
J1
SPS Board
1
2
SGCT
Test Point
Resistance Value between two
heat sinks is sharing resistance
in parallel with Anode-Cathode
Resistance