Terminal/connections descriptions – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control User Manual
Page 130

130
Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014
Chapter 3
Component Definition and Maintenance
Terminal/Connections Descriptions
P1 – DC Input
PIN NO.
LABEL
DESCRIPTION ONLY
1
+56V
+56V input
2
+56V COMM
+56V common
3
EARTH
earth ground
P2 – SENSE
(To ACB)
PIN NO.
LABEL
DESCRIPTION ONLY
1
+56V
+56V input supply
2
+56V RTN
+56V input supply return
3
NC
Not Connected
4
NC
Not Connected
5
+24V
Isolated +24V Supply
6
+24V RTN
Isolated +24V Supply return
7
NC
Not Connected
8
NC
Not Connected
9
+5VA
Primary +5V supply, before OR’ing diode
10
DGND (com1)
+5V, +/-15V Common
11
+5VB
Secondary +5V supply, before OR’ing diode
12
DGND (com1)
+5V, +/-15V Common
13
ID0
Power Supply ID Pin 0
14
ID1
Power Supply ID Pin 1
P3 – ISOLATOR
(To Isolator
Modules)
PIN NO.
LABEL
DESCRIPTION ONLY
1
ISOLATOR
(+24V,1A)
+24V, 1A/com4
2
ISOL_COMM
(com4)
0V/com4
3
EARTH
EARTH
P4 – PWR
(To ACB)
PIN NO.
LABEL
DESCRIPTION ONLY
1
+24V_XIO
(+24V,2A)
+24V, 2A/com3
2
XIO_COMM
(com3)
0V/com3
3
+HECSPWR
(+24V,1A)
+24V, 1A/com2
4
LCOMM (com2)
0V/com2
5
–HECSPWR (-
24V,1A)
-24V, 1A/com2
6
+15V_PWR
(+15V,1A)
+15V, 1A/com1
7
ACOMM (com1)
0V/com1