Snubber capacitance – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control User Manual

Page 74

Advertising
background image

74

Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014

Chapter 3

Component Definition and Maintenance

Snubber Capacitance

Turn the multimeter from the resistance to capacitance measurement mode.
Verify the snubber capacitor by measuring from the test point to the heat sink
adjacent to the right for standard rectifiers, or from heat sink to heat sink. For
SPS rectifiers, measure from the test point to pin 1 of the Phoenix connector that
plugs into J1 of the SPS board (disconnect the J1 connector from the SPS board
first).

Figure 60 - Snubber Capacitor Test

Figure 61 - Snubber Capacitor Test (shown with SPS Board installed)

Heatsink

Heatsink

Snubber
Resistor

Snubber
Capacitor

Sharing Resistor

Test Point

Measure capacitance
between heat sink and
test point (or heat sink
to heat sink)

Snubber test point

SGCT

Heatsink

Heatsink

Snubber
Resistor

Snubber
Capacitor

Sharing Resistor

J1

SPS Board

1

2

SGCT

Test Point

Snubber Capacitor Wire

Use Connector Terminal Screw
for Testing Snubber Capacitor

SGCT Cathode Wire

Snubber
Test
Point