Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control User Manual

Page 173

Advertising
background image

Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014

173

Preventative Maintenance Schedule

Appendix C

PowerFlex 7000 Preventative
Maintenance Service
Schedule

Interval Period (in years)

0

1

2

3

4

5

6

7

8

9

10

Commissioning Activities

S

Air-Cooling

System

n

Door Mounted Air Filters

ou

C/R C/R C/R C/R C/R C/R C/R C/R C/R C/R C/R

Main Cooling Fan Motor

I

I

I

I

I

I

RFB/R

I

I

I

Redundant Cooling Fan Motor (if supplied)

I

I

I

I

I

I

RFB/R

I

I

I

Small Aux. Cooling Fans “Caravel”

I

I

I

I

R

I

I

I

I

R

Liquid-Cooling

System

p

Mesh Filters

u

C C C C C C C C C C C

De-ionizing Filter Cartridge

u

R R R R R R R R R R R

All

Fittings/Connections/Hose

Clamps

I I I I I I I I I I

Redundant Cooling Pump Motors/Pumps

I

I

I

I

I

I

I

I

I

I

Redundant Cooling Pump Motor Seals

I

I

I

I

I

I

I

I

I

R

Thermostatic

Valve

Element

I I I I I I R I I I

Power Switching

Components

Power Devices (SGCTs/SCRs)

I

I

I

I

I

I

I

I

I

I

Snubber

Resistors/Sharing

Resistors/HECS

I I I I I I I I I I

Rectifier Snubber Capacitors

I

I

I

I

q

I

I

I

I

q I Rv/R

q

Inverter Snubber Capacitors

I

I

I

I

I

I

I

I

I

R

Integrated Gate Driver Power Supply

I

I

I

I

RFB/R

I

I

I

I

RFB/R

Self-Powered SGCT Power Supply (SPS)

I

I

I

I

RFB/R

I

I

I

I

RFB/R

Integral

Magnetics/Power

Filters

Isolation

Transformer/Line

Reactor

I I I I M I I I I M

DC Link/Common Mode Choke

I

I

I

I

M

I

I

I

I

M

Line/Motor Filter Capacitors

I

I

I

I

M

I

I

I

I

M

Control Cabinet

Components

AC/DC and DC/DC Power Supplies

I

I

I

I

RFB/R

I

I

I

I

RFB/R

Control

Boards

I I I I I I I I I I

Batteries (DCBs and CIB)

I

I

R

I

I

R

I

I

R

I

Battery Module (UPS)

r

I I I I R I I I I R

Connections

Low Voltage Terminal Connections/
Plug-in Connections

I I I I I I I I I I

Medium

Voltage

Connections

I I I I I I I I I I

Heatsink

Bolted

Connections

I I I I I I I I I I

Medium Voltage Connections (Rectifier)

s

I

q

I

q

I

q

Medium Voltage Connections (Inverter)

t

– – – – – – – – – I

Enhancements

Firmware

– – Rv – – Rv – – Rv –

Hardware

– – Rv – – Rv – – Rv –

Operational

Conditions

Parameters

I I Rv I I Rv I I Rv I

Variables

I I Rv I I Rv I I Rv I

Application

Concerns

I I Rv I I Rv I I Rv I

Spare Parts

Inventory/Needs

I I Rv I I Rv I I Rv I

n

Only applies to air-cooled VFDs (i.e. ‘A’ Frame and ‘B’ Frame)

o

If filter supplied is not a washable type, replace filter. If filter supplied is a washable type, wash or replace (depending on state of filter).

p

Only applies to liquid-cooled VFDs (i.e. ‘C’ Frame)

q

A 4 year replacement interval applied to all 6-pulse and 18-pulse rectifier versions with previously available rectifier snubber capacitors. Snubber capacitors now
available extend the replacement period of “B” and “C” frames to 10 years (replacement period for “A” Frames remain at 4 years) – contact Cambridge for details and
to purchase extended life snubber capacitors. Active Front End rectifiers have a 10 year rectifier snubber capacitor replacement interval.

r

Replace UPS battery module yearly for 50°C rated VFDs.

s

When rectifier snubber capacitors are replaced, the MV connections for rectifier need to be inspected.

t

When inverter snubber capacitors are replaced, the MV connections for inverter need to be inspected.

u

These components may be serviced while the VFD is running.

Advertising