Ground filter component replacement – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control User Manual
Page 97

Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014
97
Component Definition and Maintenance
Chapter 3
Ground Filter Component Replacement
The number of capacitors will vary depending on the system voltage.
1.
Ensure there is no power to the equipment.
Note the position of the leads.
2.
Disconnect the leads connected to the failed capacitor/resistor bank.
3.
Loosen and remove mounting screws as indicated in
and remove
the failed component.
4.
Assemble the new component in the reverse order of disassembly.
5.
Reattach the leads strictly adhering to the torque requirements outlined
below.
Figure 83 - Ground Filter Component Replacement
ATTENTION: To prevent electrical shock, ensure the main power has been
disconnected before working on the capacitor. Verify that all circuits are voltage
free using a hot stick or appropriate voltage-measuring device. Failure to do so
may result in injury or death.
IMPORTANT
The maximum torque for the capacitor terminal is 3.4 N•m (30 lb•in.).
Capacitors
Resistor Bank
Reactor Transformer
Reactor Transformer Barrier