Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control User Manual

Page 134

Advertising
background image

134

Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014

Chapter 3

Component Definition and Maintenance

Diagnostic test points on the DPM have a voltage output range of -5 to +5V. The
following is the list of test points on the DPM:

This table defines the states of LEDs D9 and D11 on the DPM board. D9 is used
for the Inverter side processor and D11 is for the Rectifier side processor. The
other two LEDs (D6 and D7) are the watchdogs for the Inverter and Rectifier
code respectively.

Table 3 - Test Points on Drive Processor Module

Test points

Name

Description

DPM-TP1

+1.2V

+1.2V DC power supply

DPM-TP2

+1.8V

+1.8V DC power supply

DPM-TP3

+2.5V

+2.5V DC power supply

DPM-TP4

+3.3V

+3.3V DC power supply

DPM-TP5

+5V

+5V DC power supply

DPM-TP6

DGND

Digital ground

DPM-TP8

ITP1

Digital to Analog output – Assignable diagnostic test point

DPM-TP9

ITP2

Digital to Analog output – Assignable diagnostic test point

DPM-TP10

ITP3

Digital to Analog output – Assignable diagnostic test point

DPM-TP7

ITP4

Digital to Analog output – Assignable diagnostic test point

DPM-TP11

RTP4

Digital to Analog output – Assignable diagnostic test point

DPM-TP12

RTP3

Digital to Analog output – Assignable diagnostic test point

DPM-TP13

RTP2

Digital to Analog output – Assignable diagnostic test point

DPM-TP14

RTP1

Digital to Analog output – Assignable diagnostic test point

Table 4 - Description of D9 and D11 Function

Color

Rate of Count (Pulse)

Meaning

Green

10 Count

PreExecution OK

Red

0.25 Hz

No Bootcode

Green

0.25 Hz

No Application

Green

0.5 Hz

Downloading via Serial Port

Green

2 Hz

Serial Port Active – i.e. Terminal

Green

1 Hz

Waiting/Loading Application

Green

Solid

Operation Running or Successful

Red

Solid

Operation Failed

Red

2 Count

POST – RAM Failed

Red

3 Count

POST – NVRAM Failed

Red

4 Count

POST – DPRAM Failed

Red

8 Count

FPGA Loading Failed

Red

9 Count

POST – USART Failed:
1 Green Count = Port 1
2 Green Count = Port 2

Red

10 Count

End of Code Reached

Red

11 Count

Download – CRC Error

Red

14 Count

Download – Overflow Error

Advertising