Component Definition and Maintenance
Chapter 3
Replacement Procedure for DC/DC Power Supply
(Refer to
1.
With the drive energized, check that all output voltages are present
(View 1).
2.
De-energize the drive, isolate and lock out the control power, and remove
all wire connections from the unit (View 1).
3.
Remove quantity of four M6 (H.H.T.R.S.) that will allow the DC/DC
Power Supply Assembly to be removed from the Low Voltage Panel.
(View 1).
4.
Remove quantity of four M4 (P.H.M.S.) and Nylon Shoulder Washers
from the back of the Mounting Plate (View 2).
5.
Replace old DC/DC Power Supply with the new one.
Ensure the Black Insulation is between the DC/DC Power Supply and
the Mounting Plate. Repeat steps 4 through 1 in this order to replace unit
(View 2).
6.
Ensure the ground wire of P4 plug is connected to the ground by
M10 bolt.
8
-15V_PWR (-
15V,1A)
-15V, 1A/com1
9
+5V_PWR
(+5V,5A)
+5V, 10A/com1
10
DGND (com1)
0V/com1
11
EARTH
earth ground