139

Component Definition and Maintenance

Chapter 3

Table 6 - Test Points on Analog Control Board

Test points

Name

Description

ACB-TP1

Vuv

Motor Voltage Feedback, UV

ACB-TP2

Vvw

Motor Voltage Feedback, VW

ACB-TP3

Vwu

Motor Voltage Feedback, WU

ACB-TP4

Iu

Motor Current, HECSU

ACB-TP5

Iw

Motor Current, HECSW

ACB-TP6

Vzs

Zero Sequence Generation Motor side, VZS

ACB-TP7

Vn

Motor Side Filter CAP Neutral Voltage, MFCN

ACB-TP8

V_pk

Motor Over Voltage Detection for UVW

ACB-TP9

Vdci1

Motor Side DCLINK Voltage for Bridge #1, VMDC1

ACB-TP10

Vdci2

Motor Side DCLINK Voltage for Bridge #2, VMDC2

ACB-TP11

Vuvs

Line Voltage Synchronous Feedback, VSAB

ACB-TP12

V2uv

Line Voltage Feedback, 2UV

ACB-TP13

V2vw

Line Voltage Feedback, 2VW

ACB-TP14

V2wu

Line Voltage Feedback, 2WU

ACB-TP15

I2u

Line current, CT2U

ACB-TP16

I2w

Line current, CT2W

ACB-TP17

Vzs2

Zero Sequence Generation Line side, VZS2

ACB-TP18

Vn1

Line Filter CAP Neutral Voltage for Bridge #1, LFCN1

ACB-TP19

V2_pk

AC over voltage detection for 2UVW

ACB-TP20

Vdcr1

Line side DCLINK Voltage for Bridge#1,VLDC1

ACB-TP21

Idc1

DCLINK current, HECSDC1

ACB-TP22

Vvws

Line Voltage Synchronous Feedback, VSBC

ACB-TP23

V3uv

Line Voltage Feedback, 3UV

ACB-TP24

V3vw

Line Voltage Feedback, 3VW

ACB-TP25

V3wu

Line Voltage Feedback, 3WU

ACB-TP26

I3u

Line current, CT3U

ACB-TP27

I3w

Line current, CT3W

ACB-TP28

Vzs3

Zero Sequence Generation Line side, VZS3

ACB-TP29

Vn2

Line Filter CAP Neutral Voltage for Bridge #2, LFCN2

ACB-TP30

V3_pk

AC over voltage detection for 3UVW

ACB-TP31

Vdcr2

Line side DCLINK Voltage for Bridge#2, VLDC2

ACB-TP32

Idc2

DCLINK current,HECSDC2

ACB-TP33

Vwus

Line Voltage Synchronous Feedback, VSCA

ACB-TP34

V4uv

Line Voltage Feedback, 4UV

ACB-TP35

V4vw

Line Voltage Feedback, 4VW

ACB-TP36

V4wu

Line Voltage Feedback, 4WU

ACB-TP37

I4u

Line current, CT4U

ACB-TP38

I4w

Line current, CT4W

ACB-TP39

Vzs4

Zero Sequence Generation Line side, VZS4 (spare one)

ACB-TP40

Vnn

CMC Neutral Voltage, VNN

ACB-TP41

Inn

CMC Neutral current, INN

ACB-TP42

Ignd

Ground Fault current, GFCT