Chapter 2

Drive Installation

Figure 34 - Ground Connection Diagram with Isolation Transformer

Figure 35 - Ground Connection Diagram with Line Reactor

Each power feeder from the substation transformer to the drive must be provided
with properly sized ground cables. Utilizing the conduit or cable armor as a
ground is not adequate.

Note that if a drive isolation transformer is used, the WYE secondary neutral
point should not be grounded.

Each AC motor frame must be bonded to grounded building steel within 6 m
(20 ft) of its location and tied to the drive's ground bus via ground wires within
the power cables and/or conduit. The conduit or cable armor should be bonded
to ground at both ends.

ISOLATION

TRANSFORMER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

Connected to the neutral point
of the output capacitor

OUTPUT

GROUND

NETWORK

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

AC LINE

REACTOR

TRANSFORMER

Connected to the neutral point
of the output capacitor

GROUND

FILTER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

AC LINE

REACTOR

TRANSFORMER

Connected to the neutral point
of the output capacitor

GROUND

FILTER