122

Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014

Chapter 3

Component Definition and Maintenance

Output Calibration

Ensure the output of the supply is 56V DC.

There is a potentiometer on the top of the power supply that adjusts the 56 V DC
output for the power supply. Isolate the output of the power supplies; multiple
supplies in series will affect your measurements. With the control power on and the
output of the AC/DC Converter isolated from the drive control, adjust the
potentiometer until the output equals 56V DC. Perform this test on each power
supply. When all adjustments are complete, re-connect the power supply to the
circuit and re-measure the output. Readjust if necessary.

If it is not possible to maintain 56V DC, the power supply may be faulty.

Power Supply Replacement

1.

Ensure control power has been isolated and locked out.

2.

Disconnect the terminals at the unit.

3.

Remove the four M6 bolts per

Figure 102

or

Figure 103

.

4.

Extract the power supply complete with bracket from the drive.

5.

Remove the bracket(s) from the failed power supply (four M4 screws and
nylon shoulder washers).

6.

Attach bracket to replacement power supply. The Black Insulation(s) must
be between the AC/DC power supply and the mounting plate(s).

7.

Repeat Steps 5 through 1 in this order to replace the unit (

Figure 102

or

Figure 103

).

8.

Reapply control power and verify voltage levels.

P1-AC Input

PIN#

LABEL

AC (L)

Live

AC (N)

Neutral

NC

No Connection

FG

Earth

P2-DC Output

PIN#

LABEL

+

+56V

+56V COMM

P3-Fail Output

PIN#

LABEL

CN1

1-2 Connected
3-4 Connected
5, 6, 7, 8, 9, 10 N/C

CN2

N/C

CN3

7 - Alarm
8 - Alarm GND