Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014

Chapter 3

Component Definition and Maintenance

5.

Before installing the new UPS, the internal battery must be connected.

(1)

a. Remove the UPS front cover. Push down on the top of the cover and

pull the cover towards you to unclip it from the cabinet.

b. Connect the white connectors together, connecting red to red, and

black to black. Verify there is a proper connection.

c. Remove and retain the two screws from the screw mounts.
d. Place the battery connector between the screw mounts. Reinstall the

two screws to hold the connector in place.

e. Replace the UPS front cover.

Figure 105 - Connect the internal UPS battery

6.

Reconnect all the connections removed in the previous steps.

7.

Before reconnecting the mounting bracket, apply control power to the unit
and ensure the UPS is configured for the AS400 communication protocol.
Refer to the manual that comes with the UPS for instructions.

8.

Once this has been confirmed, install the mounting bracket.

(1) Reprinted from 700-3000 VA User’s Guide by permission of Eaton Corporation.