Isolated process receiver – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control User Manual

Page 143

Advertising
background image

Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014

143

Component Definition and Maintenance

Chapter 3

Isolated Process Receiver

These inputs are individually configurable to accept either a -10/0/+10V input
signal or a 4...20 mA signal. When configured for voltage input, each channel has
an input impedance of 75 k. When used as a current loop input, the transmitter
must have a minimum loop compliance of 2V to satisfy the 100 input
impedance. Regardless of input configuration, each input is individually isolated
to ± 100V DC or 70V RMS AC.

Figure 115

shows a block diagram of the receiver.

Figure 115 - Process Loop Receiver Block Diagram

The receiver can accept 4-wire transmitters.

Figure 116

shows the recommended

connections. Again, the type of shielded cable used is application specific as per
the transmitter. Pin numbers shown are for connection to the first of three
isolated process receivers.

Figure 116 - Process Loop Receiver Connections

4,8,12

3,7,11

ŀ/#

X1

U1

FPGA

DSP

1

st

I/P pins

3

rd

I/P pins

2

nd

I/P pins

A/D

Buffer

2,6,10

1,5,9

Isolation Amplifier

+

+

-

-

VPP

GND

Out

RTN

DC

IFM

1
3

2

4

User supplied power

(Sinking )

4-Wire Transmitter