Install a ControlNet Communication Module 13

To connect the PanelView Plus or PanelView Plus CE ControlNet
communication module directly to a ControlNet network as shown in
the illustration follow the instructions in these publications:

• ControlNet Coax Tap Installation Instructions, publication

1786-IN007.

• ControlNet Coax Media Planning and Installation Manual,

publication CNET-IN002.

Connect the Module Directly to a ControlNet Network

IMPORTANT

If you connect the product to a cable system that
does not support redundant media, connect the tap
dropline to the BNC connector labeled Channel A.
Channel B is left unconnected.


If the cable system is redundant, connect the product
so that all devices on the network use the same cable
for the same channel. That is, all Channel A
connectors connect to one cable; all Channel B
connectors connect to the other cable.

TIP

If you use a non-redundant cable system, all
ControlNet devices must be on the same channel,
Channel A.

PanelView Plus or
PanelView Plus CE
with 2711P-RN15S

1786-TPR, -TPS, -TPYR, or -TPYS tap

ControlNet network