Rockwell Automation 2711P ControlNet Communications for PanelView Plus and PanelView Plus CE User Manual

Page 37

Advertising
background image

Publication 2711P-UM003B-EN-P - March 2007

Configure Scheduled Communications 37

Configure the Producer Connection for the PanelView Plus/PanelView Plus CE

Configure the PanelView Plus producer connection for the
Input_From_PVP tag to be consumed by the ControlLogix processor.

1. In the Scanlist Configuration dialog, right-click on the PanelView

Plus (address 2) and select Insert Target for Connections.

2. In the Insert Target for Connections dialog, configure the

producer connection for the Input_From_PVP tag and click OK.

a. Set the Output Size to 2.

b. Set the Output Address and Status Address to 0.

c. Set the Producer Buffer ID to 1.

• The Output Size parameter (in words) must match the

Input_From_PVP tag size configured in RSLogix5000 which is
defined as type DINT. Two words (a word or integer is
equivalent to a 16-bit value) equal one DINT (double integer or
one 32-bit value).

• The Output Address and Status Address fields are used in the

RSView Machine Edition application.

• The Produce Buffer ID of this connection corresponds to the

Input_From_PVP tag’s Remote Data number that was configured
in the RSLogix 5000 Tag Properties \ Connection dialog.

PV Plus CE ControlNet - Scanlist Configura

Advertising