Configure Scheduled Communications 37
Configure the Producer Connection for the PanelView Plus/PanelView Plus CE
Configure the PanelView Plus producer connection for the
Input_From_PVP tag to be consumed by the ControlLogix processor.
1. In the Scanlist Configuration dialog, right-click on the PanelView
Plus (address 2) and select Insert Target for Connections.
2. In the Insert Target for Connections dialog, configure the
producer connection for the Input_From_PVP tag and click OK.
a. Set the Output Size to 2.
b. Set the Output Address and Status Address to 0.
c. Set the Producer Buffer ID to 1.
• The Output Size parameter (in words) must match the
Input_From_PVP tag size configured in RSLogix5000 which is
defined as type DINT. Two words (a word or integer is
equivalent to a 16-bit value) equal one DINT (double integer or
one 32-bit value).
• The Output Address and Status Address fields are used in the
RSView Machine Edition application.
• The Produce Buffer ID of this connection corresponds to the
Input_From_PVP tag’s Remote Data number that was configured
in the RSLogix 5000 Tag Properties \ Connection dialog.