Publication 2711P-UM003B-EN-P - March 2007

46 Configure Scheduled Communications

Identify Where the Input Data is Coming From

Identify where the raw input data is coming from by creating an Alias
to allow RSView Machine Edition to use this data.

1. Right-click on 0-3 Bytes under Input and select Add Alias.

2. In the Alias Properties Dialog, select the Alias Data Type DINT,

set these properties, and then click OK.

a. Alias Name = Input

b. Start Byte = 0

c. Array Count = 1

d. and specify the address.