Rockwell Automation 2711P ControlNet Communications for PanelView Plus and PanelView Plus CE User Manual
Page 39
Advertising
Publication 2711P-UM003B-EN-P - March 2007
Configure Scheduled Communications 39
2. In the Connection Properties dialog, configure the producer
connection properties for the Output_to_PVP tag and click OK.
a. Set the Input Size to 2.
b. Set the Input Address and the Status Address to 0.
• The Input Size parameter (in words) must match the
Output_to_PVP tag size. Two words (a word or integer is
equivalent to a 16-bit value) equal 1 DINT (double integer or
one 32-bit value).
• The Input Address and Status Address fields are used in the
RSView Machine Edition application.
When finished, the resulting scanlist configuration screen looks
similar to this:
PV Plus CE ControlNet - Scanlist Configuration