Install module on 400-600 terminals – Rockwell Automation 2711P ControlNet Communications for PanelView Plus and PanelView Plus CE User Manual
Page 9

Publication 2711P-UM003B-EN-P - March 2007
Install a ControlNet Communication Module 9
To replace a communication module:
1. Disconnect power from the terminal.
2. Disconnect communication cables from the communication
module.
3. Remove the four screws that secure the communication module
to the logic module.
4. Carefully lift the communication module away from the logic
module and set aside.
5. Follow steps 4 to 7 in the Install a communication module
procedure.
Install Module on 400-600
Terminals
To install a communication module:
1. Disconnect power from the terminal.
2. Set the terminal, display side down, on a clean, flat, stable
surface.
Screw
Attached Communication Module
WARNING
If you connect or disconnect any communication
cable with power applied to this module or any
device on the network, an electrical arc can occur.
This could cause an explosion in hazardous location
installations. Be sure that power is removed or the
area is nonhazardous before proceeding.