18 Configure Unscheduled Communications

8. Right-click on 1756-CNBR/D and select Add Device.

9. In the Device Properties dialog, set the address (or ControlNet

node address) to 1. This is the physical address of the
1756-CNBR/D scanner card.

10. Right-click on the ControlLogix chassis labeled 1756-A17/B and

select Properties.

11. In the Network Properties dialog, set the address of the

1756-A17/B to 2 and click OK. This is the slot in which
1756-CNBR/D is physically located.

12. Right-click on the ControlLogix chassis 1756-A17/B and select

Add Device.