Configure Unscheduled Communications

Objectives

This chapter shows how to configure a sample ControlNet network
using Unscheduled messaging between a PanelView Plus or
PanelView Plus CE terminal and an Allen-Bradley controller.

Configuring Unscheduled messaging is similar to setting up Ethernet
communications. You do not need to configure settings in the
ControlNet scanner module or use RSNetWorx to configure the
network. Unscheduled communications uses the left over bandwidth
of the ControlNet network to establish its communications.

Software Requirements

Verify that the correct software/firmware is installed on the
development computer and the PanelView Plus or PanelView Plus CE
terminal.

ControlNet Unscheduled Communications

Software/Firmware

PanelView Plus 700-1500

PanelView Plus CE 700-1500

PanelView Plus 400 or 600

RSView Studio

v3.10 or later

v4.0 or later

RSView Machine Edition Runtime

v3.10 or later

v4.0 or later

ControlNet Module Firmware

2711P-RN15S, Series A, Rev A
(firmware v2.07 or later)

(1)

2711P-RN15C, Series A, Rev A
or later

(1)

This applies to terminals that are ordered as pre-configured units with the ControlNet module.