Rockwell Automation 2711P ControlNet Communications for PanelView Plus and PanelView Plus CE User Manual

Page 45

Advertising
background image

Publication 2711P-UM003B-EN-P - March 2007

Configure Scheduled Communications 45

Configure the Input Connection

1. Under Inputs, right click on 0-3 Bytes and select Add

Connection.

2. In the Connection Properties dialog, set these properties and

click OK.

a. Start Byte = 0

b. Length in Bytes = 4

c. Status Address = 2

d. Node (MAC ID) = 1

e. Slot = 0

The PanelView Plus will read 1 DINT from a ControlLogix
processor located in slot 0 via a ControlNet scanner module
addressed at node 1, and the Status Address is assigned by
RSNetWorx for ControlNet.