Configure Scheduled Communications 27
2. In the Tag Properties dialog, configure the Input_From_PVP tag
with the Tag Type=Consumed and Data Type=DINT. The
processor will be a consumer of data from the PanelView Plus.
3. On the Connections tab, configure the connection properties of
this consumed tag so that the device producing the data is PVP,
the Remote Data value is 1, and the Request Packet Interval
(RPI) is 20 ms. When finished, click OK.
• The Remote Data value is a connection ID that must correspond
to the PVP producer connections configured in RSNetWorx.
• The Requested Packet Interval (RPI) value is determined by how
often you want a particular piece of I/O or Scheduled
peer-to-peer data to be transmitted within the Scheduled
bandwidth of the Network Update Interval.