Publication 2711P-UM003B-EN-P - March 2007

Configure Scheduled Communications 51

3. Configure the same shortcut for the Target tab.

A simple way to do this is by selecting Copy. This copies the
configuration of the Local tab to the Target tab.

4. Verify that no devices are configured for Ethernet

communications in the Target tab. If devices exist for Ethernet
communications in the Target tab, delete the devices but keep
the Ethernet driver.

5. Click OK when done.

ControlNet Scheduled communications is now configured. Develop
the rest of the RSView Machine Edition application using this
communication configuration. A sample ControlNet Scheduled
communication application is available on the Rockwell Automation
Technical Support Knowledgebase in Technote A103053983 at
http://support.rockwellautomation.com.

Address Assignments for Objects

Tag addresses are assigned to objects in the Tag Browser.

To access the Tag Browser:

1. Select an object and then select the Connections tab. To do this,

either:

• right-click on object and select Connections
• double-click to open the object’s Properties dialog and select

the Connections tab.

2. Click on tag to open the Tag Browser.

3. Open the path to the CNET_SCHEDULED tags.

The folder is <application name><shortcut>Online and either
Input Table or Output Table.

The Input Table folder is used for input data received by the
PanelView Plus/PanelView Plus CE device from another device.
The Output Table folder is used for output data that is sent from
the PanelView Plus/PanelView Plus CE device to another device.