48 Configure Scheduled Communications
Configure the Output Connection
1. Under Outputs, right click on 0-3 Bytes and select Add
Connection.
2. In the Connection Properties dialog, set these properties and
click OK.
a. Start Byte = 0
b. Length in Bytes = 4
c. Status Address = 2
d. Node (MAC ID) = 1
e. Slot = 0
The PanelView Plus will send 1 DINT to the ControlLogix processor
located in slot 0 via a ControlNet scanner module addressed at node
1. The Status Address is assigned by RSNetWorx for ControlNet.