44 Configure Scheduled Communications
Configure I/O for the PanelView ControlNet Module
Configure the 2711P-RN15x to scan the specific size of inputs and
output. This I/O configuration method is very similar to RIO. Perform
this operation from the I/O Configuration tab.
Configure the Input Scan Size for the Module
1. On the I/O Configuration tab, right-click on Input and select
Add Address Block.
2. In the Address Block Properties dialog, set these properties and
click OK.
a. Start Byte=0
b. Length in Bytes = 4
The PanelView Plus will read 1 DINT from the ControlLogix
processor beginning at byte 0.