Configure Scheduled Communications 29

3. In the Tag Properties dialog, configure the Output_To_PVP tag

with the Tag Type=Produced and Data Type=DINT.

4. On the Connection tab, set the number of Maximum Consumers

to 1 and click OK.

If this specific data is going to be consumed by many PanelView
Plus terminals, enter the number of terminals that would be
receiving this data.

5. Save the ladder logic program, download the ladder to the

ControlLogix processor, and put the processor in Run mode.

The ControlLogix processor is configured and ready to produce and
consume data from the PanelView Plus. Next, configure the
ControlNet network using RSNetWorx for ControlNet.