Configure plc ladder logic file – Rockwell Automation 2711P ControlNet Communications for PanelView Plus and PanelView Plus CE User Manual
Page 23
Advertising
Publication 2711P-UM003B-EN-P - March 2007
Configure Scheduled Communications 23
Configure PLC Ladder Logic
File
To take advantage of ControlNet Scheduled messaging, you need to
configure the PLC ladder logic file so that it knows which tags are
producers and consumers of data from the PanelView Plus /
PanelView Plus CE. These tags are typically configured as Controller
Tags, because a Program Tag cannot be configured as a consumer.
Procedures in this chapter will show how to configure existing DINT
type Controller Tags in a 1756-L63 ControlLogix Processor to be
producers and consumers:
• Output_to_PVP (Producer)
• Input_from_PVP (Consumer)
Advertising