Rockwell Automation 2711P ControlNet Communications for PanelView Plus and PanelView Plus CE User Manual
Page 43
Advertising
Publication 2711P-UM003B-EN-P - March 2007
Configure Scheduled Communications 43
3. From the Local tab, right click on 1789-A17, Backplane and
select Add Device.
4. Select 2711P-RN15S (or 2711P-RN15C) and click OK.
5. In the ControlNet Scanner Properties dialog, configure the
2711P-RN15x communication module and click OK.
a. Name = ControlNet Scanner Card for PanelView
Plus/PanelView Plus CE
b. Node Address = 02
c. Slot in Virtual Backplane = 01.