34 Configure Scheduled Communications

Configure RSNetworx for ControlNet

1. Open RSNetWorx for ControlNet by selecting Start Menu >

Programs > Rockwell Software > RSNetWorx > RSNetWorx for
ControlNet

2. Select the Enable Edits box.

If you are using RSNetWorx for ControlNet with RSLogix 5000,
select enable edits to import the external connection information
from RSLogix 5000.

3. Browse the ControlNet network to find the devices that need to

be configured. Select the icon or Network > Online.

If the configuration computer is not connected directly to the
ControlNet network, you can gain access to the network via
Ethernet to a 1756-ENBT module as shown.