Half duplex (2-wire), Full duplex (4-wire) – Holtgreven GSE-375 User Manual

Page 14

Advertising
background image

8

Table 2-1: RS-485 Comm Port 1 Connections

Comm port 1 pin out

Connection

1 No

connection

2 TX

(B+)

3 TX

(A-)

4 VCC
5 ISO

ground

6 Ground
7 RX

(A-)

8 RX

(B+)

9 VCC

Half Duplex (2-wire)

Installing jumpers 1, 2 and 4 on the RS-485 option board electrically connects pin RX B(+) to pin
TX B(+), and pin RX A(-) to pin TX A(-) on the option board. This effectively provides two + and
two - pin connections, enabling easy connection of network lines in parallel from device to device
without having to position two wires into the same lever socket. A B(+) line from each device on
the network should be connected in parallel to the next device on the network. This is also true for
all A(-) lines.

The units inside the two end-points of the network loop will utilize both A(-) pin connections and
both B(+) pin connections. The units at the end-points of the network will utilize only one A(-) pin
connection and one B (+) pin connection.

Full Duplex (4-wire)

Removing jumpers 1, 2 and 4 on the RS-485 option board requires that the transmit and receive
lines be wired independently of one another. The RX B(+) and RX A(-) receive lines must be
wired in parallel to the next device's RX B(+) and RX A(-) receive lines and the TX B(+) and TX A
(-) transmit lines must be wired in parallel to the next device's TX B(+) and TX A(-) transmit lines.

Advertising