Figure 2-2: Model 370/375 Analog Output and Setpoint Option Installation

Analog Output Connections

Pin

Connection Name

Description

1 Earth

Ground

Non-isolated earth ground (future use).

2

+ 5 VDC

Isolated 5 volt source (future use).

3

Isolated Ground

Provides an isolated ground connection.

4

Vout

Used for the 0-10 VDC analog signal output.

5

Isolated Ground

Provides an isolated ground connection.

6

Iout

Used for 4-20 or 0-20 mA analog signal output.

S

S

e

e

t

t

p

p

o

o

i

i

n

n

t

t

O

O

p

p

t

t

i

i

o

o

n

n

The setpoint option provides the ability to running a process, turning on stack lights or anything
else that may require an output signal. Eight different configurations are offered. Requires an
option mounting bracket kit (24370B-300A0) for internal installation.

Table 2-3: Setpoint Option Board Part Numbers

Quantity

Part Number

Description

1

420925-36594

DC 4 output

1

420926-36589

DC 4 input

1

420924-36584

CD 2/in - 2/out

1

420923-36574

Low voltage AC, 4 input

1

420918-36536

Low voltage AC, 2/in - 2/out

1

420922-36579

AC 4 output

1

420923-37093

High voltage AC, 4 input

1

420918-37092

High voltage AC, 2/in - 2/out

Installation Instructions

1.

DISCONNECT POWER! UNPLUG THE MODEL 370/375 TO INSURE DAMAGE WILL NOT
OCCUR DURING OPTION INSTALLATION

2.

Remove the (6) 38-31-8710 M5 x 0.8 x 10 mm screws from the enclosure bottom plate and
set it aside.

3.

Discard the mounting hardware provided with the setpoint option kit and use the hardware
provided with the option-mounting bracket kit. Refer to page 13 for parts included with this
kit.

4.

Snap in the (4) nylon spacers in the 4 holes either to the right of the notch or the left of the
notch in the option mounting bracket.