Parameter Setting

Description

P5142.0 ~ Act 3 ~ Above

Alarm relay activates when net weight rises above target 3.

P5143.-- ~ Targ 3 ~ =900

Target 3 = 900 kg.

P5144.0 ~ Stbl3 ~ Ignore

Alarm relay activates regardless of scale stability.

P5145.3 ~ Rset 3 ~ Non-L

Alarm relay closes when net weight falls below target 3.

P5147.0 ~ Rset3 ~ Ignore

Alarm relay closes regardless of scale stability.

T

ARGET

D

EVIATION

C

HECK

-W

EIGHING

The target deviation method uses a target value in which the upper and lower tolerances are
deviated from the target. The upper and lower tolerances are fixed values. The accept window is
varied by adding the high tolerance to the target and subtracting the low tolerance from the target.
This feature is commonly used in check-weigh applications. The desired target may be based on
gross weight, net weight or quantity (if counting is enabled). The annunciators will light on the
Model 370/375 display or physical setpoints can be added.

Table 3-12: Setpoint Setup (Target Deviation Check-Weighing)

Setpoint Selection

Function

Description

P5100.8 Checb

Target

Deviation

Mode.

P5101.-- Targ1

Target

value.

P5102.--

Lo

Low acceptance deviation.

P5103.--

Hi

High acceptance deviation.

P5104.0 Based

Select

from

Net, Gross or Quantity.

See Key-In Parameters on page 18 for instructions on using the front panel keys for entering
data.

Activation Method (Target Deviation Check-Weighing)

In order for the annunciators to activate, the displayed value must be at least five graduations
above zero.

Check-Weigh Status Annunciator Status

Annunciator Color (LED)

OVER

SP 1 Illuminated

Red

GOOD

SP 2 Illuminated

Green

UNDER

SP 3 Illuminated

Yellow



The Pre-Acts, Learn Mode, and Pause Feature options are not applicable to check-weigh operation.

Changing Targets From The Weigh Mode (Target Deviation Check-
Weighing)

When Check-Weigh by Deviation is configured in the setpoint setup, the Targ 1 value
automatically becomes an available mode for the [SELECT] key. It is possible to accept the
applied weight as the target. Instead of keying in the target value from Targ 1, press [TARE]
(370) or [SAMPLE/Enter] (375). Press [TARE] (370) or [SAMPLE/Enter] (375) again to accept
the target. Lo and Hi are the subsets for Targ 1. Lo and Hi are entered as actual values.

To change target to 10 from the Weigh Mode:

1. From the weigh mode press [SELECT] until targ1 is shown on the display.

DISPLAY READS Targ1 ~15.00

2. Press

10 [TARE] or [SAMPLE/Enter] to set a new target. Either press [SELECT] to go to the

weigh mode or go to step 3 to access the low tolerance parameter.
DISPLAY READS Targ1 ~ 10.00