4 plc link error – KEYENCE BL-600 Series User Manual

Page 152

Advertising
background image

Chapter 8 PLC Link

142

8

8.4

PLC Link Error

This section describes the remedy if a communication error occurs during the PLC
link.

If an error occurs, the BL-600 Series stops communication. The top LED in the
STABILITY indicator flashes.

1. Check the following points and eliminate the cause.

1) Check if the RS-232C communication parameters (baud rate, data length,

parity and stop bit length) for the PLC are matched with the N-400’s settings.

2) Check if the PLC link is set to “Use” in the communication parameters 2

setup.

3) Check if the PLC’s settings are correct.

See pages 132 to 134.

4) Check if the cable connections are correct, or if any cable is disconnected.

Referring to chapter 2 of this manual, check the connections using a multim-
eter.

5) Check if the device setting range does not exceed the available data

memory areas of the PLC.
If the data memory areas used for the BL-600 do not exist in the PLC,
communication is impossible.

6) Check if the link unit operates normally.

*

For the settings of the link unit, see the instruction manual for the link unit being
used.

2. Press the TEST switch of the BL-600 Series.

Communication recovers.

If the problem cannot be solved in the procedure above, contact your nearest
KEYENCE office or distributor (listed at the end of this manual).