2 i/o wiring – KEYENCE BL-600 Series User Manual

Page 44

Advertising
background image

Chapter 3 Connection and Installation

34

3

3.3.2 I/O Wiring

Trigger input

The trigger input is used to signal the BL-600 to start reading (start laser emission).
The trigger input is a non-voltage input (TTL input is also available with negative
logic).

Connection to a photoelectric sensor manufactured by KEYENCE

OK/NG output

The OK/NG output is used to display the comparison/verification result of the
preset data.

➮ See page 101.

When no preset data is registered, it can be used to display whether or not bar
codes are being read correctly. The output form is NPN open-collector.

Connection to a programmable logic controller (PLC) manufactured by

KEYENCE

GND

TIM

1

5

5 V DC

10 k

4.7

k

Internal circuit

BL-600

Contact or
solid-state

Circuit diagram

TIM

GND

+

1

5

BL-600

Photoelectric sensor

Brown (Red)

Black (White)

Blue (Black)

GND

OK/NG

4/6

5

Load

BL-600

10 k

* Rated load: 24 V DC
(30 mA) max.

+

Internal circuit

Circuit diagram

OK/NG

GND

+

4/6

BL-600

5

0000

C

PLC