EVCO S.p.A.

EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214

page 19 of 94

5

USER INTERFACE

5.1

Foreword

The following operating status exist:

-

the “off” status (the device is not powered)

-

the “stand-by” status (the device is powered and is off)

-

the “on” status (the device is powered, is on and is in stand-by for the start-up of an operating cycle)

-

the “run” status (the device is powered, is on and an operating cycle is in progress).

Hereon, the term "device switch-on" means the passage from the "stand-by" status to the "on" status. the term

"switch-off" means passage from the "on" status to the "stand-by" status.

If a power cut occurs during the "stand-by" status or during the "on" status, the device will re-propose the same

status when the power supply is restored.

If a power cut occurs during the "run" status, the device will operate as follows when this is restored:

-

if a temperature-controlled blast chilling or deep freezing operation was in progress, these will be started again

from the beginning

-

if a timed-controlled blast chilling or deep freezing operation was in progress, these will be started again from

the moment the power supply was cut-off

-

if storage was in progress, this will be re-proposed.

5.2

Device commissioning

Operate as follows:

1.

Connect the device power supply. if parameter E9 is set at 1, the device will display the EVCO splash screen for

10 s, after which it will go to the “stand-by” status.