5 time-controlled hard blast chilling and storage – EVCO EVFTFT818P7U Installer manual User Manual

Page 31

Advertising
background image

EVCO S.p.A.

EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214

page 31 of 94

During storage the device displays the temperature of the cabinet, the program name (if envisioned) and the duration

of blast chilling.

Parameter r10 establishes the work set-point during storage.

6.5

Time-controlled hard blast chilling and storage

The time-controlled hard blast chilling and storage cycle is divided into the following three phases:

-

blast chilling hard phase

-

blast chilling

-

storage.

On conclusion of a phase, the device passes automatically to the next.

Operate as indicated to start the cycle:

1.

Make sure the device is in the "on" status.

2.

Make sure that the keyboard is not locked and that no procedure is in progress.

3.

Press and release the

key (1), press and release the

key (2) and then press and release the

key (3).

the device will display the blast chilling duration and the work set-point during blast chilling.

4.1

Press and release the MENU key and then press and release the

key or the

key to select the blast chilling

duration and the work set-point during blast chilling.

4.2

Press and release the

key or the

key to modify these values and then the ESCAPE key to memorise them;

these values can also be memorised through parameters r1 and r7.

5.

Press and release the START/STOP key (1): the cycle will be started.

Advertising