EVCO EVFTFT818P7U Installer manual User Manual

Page 67

Advertising
background image

EVCO S.p.A.

EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214

page 67 of 94

i2

-1

120

min

5

door open alarm signalling delay (“id” code); on expiry of

the time established with the parameter, the compressor

and the evaporator fan will be off

-1 = the alarm will not be signalled

i5

0

1

- - - -

1

effect caused by the activation of the high pressure input

0 = no effect

1 = the compressor and the evaporator fan will be off

and the condenser fan will be on. On expiry of the

time established with parameter i7, the 3 digit

display will show the flashing “HP” code and the

buzzer will be activated (until the input is

deactivated)

i6

0

1

- - - -

0

type of high pressure input 1

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i7

-1

240

s

5

high pressure alarm signalling delay (“HP” code)

-1 = the alarm will not be signalled

i8

0

1

- - - -

0

type of low pressure input 1

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i9

-1

240

s

5

low pressure alarm signalling delay (“LP” code)

-1 = the alarm will not be signalled

i10

0

1

- - - -

0

type of compressor circuit breaker protection input contact

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i11

- - - -

- - - -

- - - -

- - - -

reserved

Par.

Min.

Max.

Unit

Default

Digital outputs

u1

0

1

- - - -

0

utility managed by the output K8 (15)

0 = pump down valve (in this case, parameter u12 will

have meaning)

1 = alarm output