EVCO S.p.A.

EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214

page 61 of 94

C4

0

240

min

10

duration of compressor switch-off during the cabinet probe

error (“Pr1” code) that occurs during storage; see also

parameters C5 and C9

C5

0

240

min

10

duration of compressor switch-on during the cabinet probe

error (“Pr1” code) that occurs during post blast chilling

storage; see also parameter C4

C6

0

199

°C/°F (1)

80

condenser

temperature

above

which

the

blocked

overheated condenser alarm is activated (“COH” code)

C7

0

199

°C/°F (1)

90

condenser

temperature

above

which

the

blocked

compressor alarm is activated (“CSd” code)

C8

0

15

min

1

blocked compressor alarm delay (“CSd” code) (5)

C9

0

240

min

30

duration of compressor switch-on during the cabinet probe

error (“Pr1” code) that occurs during post deep freezing

storage; see also parameter C4

Par.

Min.

Max.

Unit

Default

Defrosting (6)

d0

0

99

h

8

defrosting interval (7)

0 = defrosting will never be activated at intervals

d1

0

3

- - - -

1

type of defrosting

0 = electrical (the compressor will be switched off during

defrosting, the defrosting output will be activated

and the evaporator fan will be switched off)

1 = hot gas (the compressor will be switched on during

defrosting, the defrosting output will be activated

and the evaporator fan will be switched off)

2 = air (the compressor will be switched off during

defrosting and the defrosting output will be

activated; the evaporator fan will be switched on,

independently from the conditions of the door, i.e.

independently from the door micro switch input

status)

3 = air with door open (the compressor will be switched

off during defrosting and the defrosting output will

be activated; the evaporator fan will be switched on,

on condition that the door is open, i.e. that is on

condition that the door micro switch is active and

that the parameter i0 is set at values different to 0)