EVCO S.p.A.

EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214

page 60 of 94

r13

-99

99

°C/°F (1)

15

end temperature of the temperature-controlled hard blast

chilling phase (temperature detected by the needle probe)

r14

10

100

%

60

duration of the time-controlled hard blast chilling phase

(intended as a percentage of the value established with

parameter r1); also duration of the time-controlled soft

deep freezing phase (intended as a percentage of the value

established with parameter r2)

r15

-99

199

°C/°F (1)

65

temperature below which the count of the maximum

temperature-controlled

blast

chilling

and

maximum

temperature-controlled

deep

freezing

is

started

(temperature detected by the needle probe)

r16

0

2

- - - -

1

type of operating cycle that can be selected

0 = blast chilling and storage

1 = blast chilling and storage or deep freezing and

storage

2 = deep freezing and storage

r17

0

99

°C/°F (1)

5

"temperature detected by the needle probe - cabinet

temperature" minimum difference such to consider the first

phase of the test to verify correct insertion of the needle

probe completed successfully (consider the difference

without sign)

0 = the test will not be performed (neither first or second

phase)

r18

1

99

s

60

duration of the second phase of the test for verification of

correct insertion of the needle probe

r19

- - - -

- - - -

- - - -

- - - -

reserved

Par.

Min.

Max.

Unit

Default

Compressor protections

C0

0

240

min

0

minimum time between restoring the power supply after a

power cut, occurring during an operating cycle and

compressor switch-on

C1

0

240

min

5

minimum time between two consecutive compressor switch-

ons (3)

C2

0

240

min

3

minimum time between compressor switch-off and

successive switch-on (3)

C3

0

240

s

0

compressor switch-on minimum duration