LP

Low pressure alarm.

Solutions:

-

check the conditions of the low pressure input

-

check the value of the parameter i8.

Main consequences:

-

the compressor and the evaporator fan will be off

-

the alarm output will be activated.

CtH

Compressor circuit breaker protection alarm.

Solutions:

-

check the conditions of the compressor circuit breaker protection input

-

check the value of the parameter i10.

Main consequences:

-

the compressor will be switched off

-

the alarm output will be activated.

PF

Power supply cut-off alarm during storage (HACCP).

Solutions:

-

check the device-power supply connection

-

check the value of the parameter A10.

Main consequences:

-

the device will memorise the alarm

-

the alarm output will be activated.

COH

Condenser overheated alarm.

Solutions:

-

check the temperature of the condenser

-

check the value of the parameter C6.

Main consequences:

-

the condenser fan will be switched on

-

the alarm output will be activated.

CSd

Compressor blocked alarm.

Solutions:

-

check the temperature of the condenser

-

check the value of the parameter C7

-

disconnect the device power supply and clean the condenser.

Main consequences:

-

if the error occurs during the “stand-by” status, no operating cycles can be selected or started

-

if the error occurs during an operating cycle, the cycle will be interrupted

-

the alarm output will be activated.

ALARM

San

Sanification alarm.

Solutions:

-

check the correct insertion of the needle probe and check the value of parameters r17 and r18.

Main consequences:

-

the cycle of sanification will be stopped.