4 list of configuration parameters – EVCO EVFTFT818P7U Installer manual User Manual

Page 58

Advertising
background image

EVCO S.p.A.

EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214

page 58 of 94

11.4

List of configuration parameters

The following table illustrates the meaning of the configuration parameters.

The management of some inputs and outputs is subject to the value set with some parameters, as follows:

-

management of the needle probe is only available if parameter P3 is set at values different to 0

-

management of the evaporator probe is only available if the parameter P4 is set at 1

-

management of the condenser probe is only available if the parameter P5 is set at 1

-

management of the cabinet light is only available if the parameter u11 is set at 0

-

management of the UV light is only available if parameter u11 is set at 1.

-

management of the pump down valve is only available if parameter u1 is set at 0

-

management of the alarm output is only available if parameter u1 is set at 1.

The evaporator fan control signal can be analogue (parameter F0 set at 3) or digital (parameter F0 set at values

different to 3).

Par.

Min.

Max.

Unit

Default

Analogue inputs

CA1

-25

25

°C/°F (1)

0

cabinet probe offset

CA2

-25

25

°C/°F (1)

0

needle probe offset 1

CA3

-25

25

°C/°F (1)

0

evaporator probe offset

CA4

-25

25

°C/°F (1)

0

condenser probe offset

CA5

-25

25

°C/°F (1)

0

needle probe offset 2

CA6

-25

25

°C/°F (1)

0

needle probe offset 3

P0

0

1

- - - -

0

probe type

0 = PTC

1 = NTC

P2

0

1

- - - -

0

temperature unit of measurement (2)

0 = °C

1 = °F

P3

0

3

- - - -

1

number of needle probe sensors

0 = needle probe not available

1 = 1 (needle probe 1)

2 = 2 (needle probe 1 and needle probe 2)

3 = 3 (needle probe 1, needle probe 2 and needle probe

3)

P4

0

1

- - - -

1

enabling the evaporator probe

1 = yes

P5

0

1

- - - -

1

enabling the condenser probe

1 = yes