EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214

page 65 of 94

F12

0

240

s

30

condenser fan switch-off delay from compressor switch-off

(only if parameter P5 is set at 0)

F15

0

240

s

15

evaporator fan delay from door closure, i.e. from the

deactivation of the door micro switch input

F16

-99

99

°C/°F (1)

20

evaporator temperature above which the evaporator fan is

off during pre-cooling, blast chilling and deep freezing (only

if parameter F0 is set at 1); see also parameter F8 (11)

F17

-99

199

°C/°F (1)

90

cabinet temperature above which the evaporator fan is off

during pre-cooling, blast chilling and deep freezing (only if

parameter F0 is set at 1 or 2); see also parameter F8

F18

0

100

%

20

evaporator fan speed 1 (intended as a percentage of the

maximum speed; sonly if parameter F0 is set at 3); see

paragraph 6.12 “Blast chilling/deep freezing intensity”

F19

0

100

%

40

evaporator fan speed 2 (intended as a percentage of the

maximum speed; sonly if parameter F0 is set at 3); see

paragraph 6.12 “Blast chilling/deep freezing intensity”

F20

0

100

%

60

evaporator fan speed 3 (intended as a percentage of the

maximum speed; sonly if parameter F0 is set at 3); see

paragraph 6.12 “Blast chilling/deep freezing intensity”

F21

0

100

%

80

evaporator fan speed 4 (intended as a percentage of the

maximum speed; sonly if parameter F0 is set at 3); see

paragraph 6.12 “Blast chilling/deep freezing intensity”

F22

0

100

%

100

evaporator fan speed 5 (intended as a percentage of the

maximum speed; sonly if parameter F0 is set at 3); see

paragraph 6.12 “Blast chilling/deep freezing intensity”