Pr4

Needle probe error 1.

Solutions:

-

the same as the cabinet probe error (“Pr1” code) but relative to the needle probe 1.

ain consequences if parameter P3 is set at 1:

-

if the error occurs during the “stand-by” status, temperature-controlled operating cycles will be

started by time-control

-

if the error occurs during temperature-controlled blast chilling, this will have duration of the

time set by parameter r1

-

if the error occurs during temperature-controlled deep freezing, this will have duration of the

time set by parameter r2

-

if the error occurs during needle probe heating, this operation will be interrupted.

-

the alarm output will be activated.

ain consequences if parameter P3 is set at 2 or at 3:

-

the device will not use needle probe 1.

Pr5

Needle probe error 2.

Solutions:

-

the same as the cabinet probe error (“Pr1” code) but relative to the needle probe 2.

Main consequences:

-

the device will not use needle probe 2.

Pr6

Needle probe error 3.

Solutions:

-

the same as the cabinet probe error (“Pr1” code) but relative to the needle probe 3.

Main consequences:

-

the device will not use needle probe 3.

rtc

Clock error.

Solutions:

-

set the real date and time again.

Main consequences:

-

the device does not memorise the date or time at which the HACCP alarm occurred or its

duration

-

the alarm output will be activated.

ErC

User interface-control module compatibility.

Solutions:

-

check that the user interface and the control module are compatible.

Main consequences:

-

the control module will continue to operate normally.

ErL

User interface-control module communication error.

Solutions:

-

check user interface-control module control module.

Main consequences:

-

the control module will continue to operate normally.