EVCO S.p.A.

EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214

page 62 of 94

d2

-99

99

°C/°F (1)

2

defrosting end temperature (evaporator temperature); see

also parameter d3

d3

0

99

min

30

if parameter P4 is set at 0, duration of defrosting

if parameter P4 is s et at 1, maximum duration of

defrosting; see also parameter d2

0 = defrosting will never be activated

d4

0

1

- - - -

0

defrosting on start-up of blast chilling and deep freezing

1 = yes

d5

0

99

min

30

defrosting delay on start-up of storing

0 = defrosting will be started on expiry of the time

established with parameter d0

d7

0

15

min

2

dripping duration (the compressor and the evaporator fan

remain off during dripping and the defrosting output will be

deactivated)

d15

0

99

min

0

minimum duration of compressor switch-on on activation of

defrosting so these can be activated (only if parameter d1 is

set at 1) (8)

d16

0

99

min

0

duration of pre-dripping (only if parameter d1 is set at 1;

the compressor and evaporator fan will be off during pre-

dripping and the defrosting output will remain activated)

Par.

Min.

Max.

Unit

Default

Temperature alarms (9) (10)

A1

0

99

°C/°F (1)

10

cabinet temperature below which the minimum temperature

alarm is activated (relative to the work set-point, i.e. “r10

A1” during post blast chilling storage and “r11 - A1” during

post deep freezing storage; (“AL” code); see also

parameter A11 (4)

A2

0

1

- - - -

1

enabling of minimum temperature alarm (“AL” code)

1 = yes