EVCO EVFTFT818P7U Installer manual User Manual

Page 68

Advertising
background image

EVCO S.p.A.

EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214

page 68 of 94

u5

-99

99

°C/°F (1)

2

cabinet temperature over which the door heating elements

are off (4)

u6

1

240

min

5

switching on UV light for sterilisation cycle duration

u7

-99

199

°C/°F (1)

40

needle probe heating end temperature (temperature

detected by the needle probe); see also parameter u8

u8

1

240

min

2

maximum duration of needle probe heating; see also

parameter u7

u9

0

1

- - - -

1

needle probe heating on opening of the door, i.e. on

activation of the door entry micro switch, which occurs after

interruption of a blast chilling and storage cycle or a deep

freezing and storage cycle during storage.

1 = yes

u11

0

1

- - - -

0

utility managed by the output K7 (15)

0 = cabinet light (in this case, the DEEP FREEZING key

and parameters i0 and u2 will assume significance)

1 = UV light (in this case, the DEEP FREEZING key and

parameter u6 will assume significance)

u12

0

999

s

10

compressor switch off delay from pump down valve

deactivation (pump down in switch-off) (17)

Par.

Min.

Max.

Unit

Default

Serial

communication

(RS-48

serial

port

with

MODBUS communication protocol)

L0

- - - -

- - - -

- - - -

- - - -

reserved

L1

1

240

min

5

recording interval during blast chilling and during deep

freezing

L2

1

240

min

15

recording interval during storage

LA

1

247

- - - -

247

device address

Lb

0

3

- - - -

2

baud rate

0 = 2,400 baud

1 = 4,800 baud

2 = 9,600 baud

3 = 19,200 baud