Interlocking – FingerTec Ingress User Manual

Page 32

Advertising
background image

32

Input point address:

To define the type of input to Ingressus to trigger fire alarm. Select Any if you are

using slave terminals as input, or Auxiliary Input Port 1 and 2. You will only find Auxiliary Input Port 1
if you are installing with Ingressus I.

9. Configure the output from Ingressus during fire alarm.

Output point address:

To define the type of action given from Ingressus during fire alarm, either Lock or

Auxililary Output. Check the box LOCK 1 and 2 if you want to control door lock during fire alarm. Select

Auxiliary 1 and 2 if you are connecting to any sensor supporting auxiliary output.

Action Type:

To define Close, Open or Normal Open as outputs from Ingressus.

Close – Ingressus outputs NC relay signal from the AUX port. The NC relay signal can turn on the 3rd party circuit,

e.g.: turning on siren to alert users.

Open – Ingressus outputs NO relay signal from AUX port. The NO relay signal can turn off the 3rd party circuit, e.g.:

turning off power to door lock system.

If you have selected Lock 1 and 2 under Output point address, select Open to unlock doors during fire alarm.
Delay – The time duration to wait before action happens.

10. Sync settings to the Ingressus controller.

Ingressus can link with motion detectors to monitor zones after operation hours. In case
of break-ins, the motion detector senses the movements of the intruder, and proceeds to
trigger its alarm output. Unlike smoke/heat sensors, motion detectors must be shut down
when users are allowed to enter the zone. You can set a schedule to activate/de-activate the
motion detector instead of manual operation.

1. Check the

Burglar Alarm

box to start configurations.

2. Select

Auxiliary Input

Disconnected

under Trigger Condition.

3. Select

Auxiliary Input 2

as Input Point Address (we recommend to connect motion detec-

tor to AUX IN 2 port).

4. Select

Auxiliary 2

under Output Point Address (we recommend to link AUX OUT 2 port to

alarm system or siren).

5. Select

Close

under Action Type.

6. Sync settings to Ingress controller.

Interlocking

This is also known as a mantrap and is only applicable for installations of Ingressus II with 2
doors. With the setting, Ingressus will detect either door closed tightly before allowing user
to verify to unlock the other door. Door sensor must be installed at each door to monitor the
door open-close activities.

1. Click

Interlocking

from the left panel.

2. Click

Add Zone

.

3.

Name

the Zone, e.g.: server rooms.

4. Click

Add Device

.