and informs you about the transmission results so that you can identify

transmission defects immediately.

•

Plug the extension cable into different sockets of the mains line you are

analyzing while continuously increasing distance to the inverter, and check

whether the communication still works. A communication breakdown from a

certain line length to the inverter on (< 30 m) indicates a disturbance from

external devices outside the household distribution (countermeasure:

suppression filter in the branch circuit).

•

Now reconnect the mains circuits one after the other and check if any errors

occur in the communication of Sunny Boy Control Light.

•

In case of communication disturbances disconnect every electric consumer on

the last connected circuit one after the other in order to identify the disturbing

device.

•

Leave disturbing devices disconnected from the mains and continue connecting

circuits and devices until all electric consumers are reconnected to the mains

except the disturbing ones.

Optimizing the Installation

•

Check whether the influence of disturbing devices can be reduced sufficiently

by just connecting them to another circuit resp. phase.

•

A junction line from the device to the Sunny Boy Control Light can help

reduce the filter expenditure in heavily disturbed installations.

Filtering Interference

•

Supply the section of the electric installation for Powerline communication with a

suppression unit.