Yaskawa DriveWizard Plus User Manual

Page 150

Advertising
background image

150

• Tune-No Rotate 1

Sets parameters related to motor characteristics without rotating the motor. Perform Tune-
No Rotate if the load cannot be disconnected from the motor for tuning purposes.

• Term

Resistance

Adjusts parameter settings for the resistance between motor lines. Sends current into the
motor coils without rotating the motor. For use when the cable between the drive and motor
exceeds 50 m, or when the length of the motor cable has changed after proper Auto-Tuning
has already been performed. Also useful for minimizing differences when the motor or drive
capacity changes.

• Parameter

Calculations

Parameter calculations require that motor-related data be entered either directly from the
motor nameplate or from the motor test report. Frequency-related values must be entered in
hertz. If online, only parameter calculations may be selected.

• Tune-No Rotate 2

The same as Tune-No Rotate 1. Perform this type of Auto-Tuning on a second motor if
used (motor 2).

• PM

Parameter

PM Motor Parameter Tuning requires that motor-related information from the motor's
nameplate or from the test report be entered.

• Z

Pulse

Z Pulse Offset Tuning calculates the Z pulse offset (

Δθ) if the PG encoder has been

replaced.