An error message may appear regardless if DriveWizard Plus is connected to a drive or not. Refer
to the check list in the table below if an error occurs.

Check Comments

Is the power on?

Is the connector loose?

Make sure the connector on the communication
cable is securely fastened.

Has the correct communication port been
selected?

Make sure that the selected port is the same port
that is connected to the communication cables.

Is the IP address setting correct?

Is should match the IP address for the controller.

Is the PC running on battery?

Serial communication problems can occur when
running a PC from the battery. Use an AC power
supply.

Is wiring correct?

For wiring instructions, refer to the instruction manual
that came with the serial communication cable and to
the instruction manual for the drive.

Is the number of node restarts set to 0?

The number of node restarts should be set greater
than 1.

Regardless of how the drives are
configured, is the number of drives properly
displayed?

Increase the number of node addresses.
If it is not possible to increase the number of
addresses, take the following steps:
• Delete the configuration set for the drive axes.
Note that this will clear parameter values that may
have been set for axis configuration.
•Set up the drives again for DriveWizard Plus.

Is the wiring for MECHATROLINK-II
correct?

Check the MECHATROLINK-II wiring.
• Wire the MECHATROLINK-II communication cable
correctly.
• Connect a terminator correctly.

Is there a problem receiving
MECHATROLINK-II data due to noise?

• Take steps to reduce noise.

This might include changing the MEHCATROLINK-II
communication cable or FG wiring, or using a ferrite
core for the communication cable.

NOTE: If DriveWizard Plus still does not properly display the drives that are connected after
going through the check list above, then try the following:

Make sure the drive’s parameters for serial communications and the SVB module setting
match.

If any changes have been made to communication-related parameters, then power to the
drive needs to be cycled to enable those changes. Note that the LED display on the drive
needs to go out completely when shutting off the power.